Joslyn Canada manufactures power transmission and distribution equipment for electric utilities - reclosers  
Joslyn Hi-Voltage manufactures power transmission and distribution equipment for electric utilities - reclosers


     

   
                                        
SmartLink?
Electrical
Operating Voltage Range: 105 - 135 Vac, 60 Hz
Surge Withstand: ANSI C62.41 - 1987
Electrostatic Discharge Test: IEC 801-2, 15 kV
Power Consumption: Less than 5 watts
FCC: Compliant
Output Relay (switch control):  
Number:
Type:

Maximum load:
Maximum Inrush:
Contact closure period:
Option 1:
Option 2:
Two
Momentary closure
Normally open
10 amps
120 Vac, 60 Hz, 50 A, 50% PF, 6 Cycles, Make Only
1-255 seconds, in 1 sec increments
Two 120 Vac NO switched contacts
Two SPST, NO isolated contact sets
Fuse Rating:
 
Controller power/output to switch: 
Battery circuit:
10A FNM Slo-Blo
3A

Status Monitoring/Control:

 

Status Inputs:






Status Outputs:

5 opto-isolated inputs mutually isolated from each other,
line and neutral(customer wetted 40V - 140V ac or dc)
or 2 dry contact inputs, internally wetted with 12Vdc,
2.5 ma with common terminal, isolated from line, neutral, chassis.

2 status outputs (solid state and isolated from each other, line and neutral) or 2 relay outputs as described in the Output Relay section above

Communications:

 

RS232 Communications port:
Optical Communications port option:
Cellemetry Transceiver Module:
Frequency:
Transmit:
Receive:

DB9 female connector
Type 2



834.390 - 835.620 MHz
879.390 - 880.620MHz

Fault Indicator Receiver (Cap Control N/A):
 
Operating Frequency:
Receiver Range: 
Certification:
312 MHz
100 feet typical (used with model 1548 FCI)
Complies with FCC Part 15 emissions
Environmental

Ambient Temperature Range:

-30°C to +55°C (outside)

Humidity Range:

0 to 95% (non-condensing)
Measurement Performance Voltage,
True RMS:
 
Secondary  
Resolution:
Accuracy:
0.2 Vac
± 0.8% of reading
Mechanical
Enclosure:
NEMA 3R, Lexan or Aluminum
Security: Latch suitable for meter seal and padlock
Mounting:
4 or 6 stab meter base (Lexan or Aluminum)
Wall or pole bracket (Aluminum)
LED Indicators:  
Red:
Red:
Red:
Green:
Red:
Processor OK
Cellular communications present indicator
Close
Trip (open)
Faulted circuit indicator (FCI)
Panel Switches: For remote/local and manual switch operation
External Antenna: Top Mounted Cellular antenna and FCI antenna
Dimensions: 8.5"h x 6.5"w x 4.75"d (Lexan)
11.5"h x 7.0"w x 4.0"d (Aluminum)
Weight: 5 lbs nominal
11 lbs Solar powered
Battery:  
Standard:
Solar:
Nickel cadmium rechargeable 10.8Vdc
Solid lead acid 12V, 2.5Ah
  

  
  
  