| AutoCap?/font> Series 4500 Controller & Recorder With Two-Way Communications | |
| Radio | |
|
Maximum Radio Dimensions:
|
13.5"h x 7.25' x 2.25"d |
| Radio
Power Supply: |
13 Vdc, 2.0A continuous, 3.0A transmit |
| Electrical | |
| Operating Voltage Ranges: | 95-140
V, 60 Hz 190-280 V, 60 Hz 95-125 V, 50 Hz 190-250 V, 50 Hz |
| Surge
Withstand: |
ANSI C62.41-1987 |
| Electrostatic Discharge Test: | 15kV applied to all accessible parts, IEC 801-2. |
| Output Relay | |
| Number: | Two |
| Type: | Momentary closure |
| Maximum Continuous Load: | 10A |
| Maximum Inrush: | 50A, 50% PF, 6 cycles, make only |
| Contact Closure Period: | Programmable 1 - 1000 seconds, in 1 sec. increments |
| Fuse Rating | |
| Output to Capacitor Switch: | 10A FNM Slo-Blo® load fuse. |
| Controller Input: | 2A controller fuse. |
| RS 232 Communications Port: | db9 female connector |
| Optical Communications Port: | Type 2 |
| Mechanical | |
| Enclosure:
|
Luran, NEMA 3R |
| Mounting:
|
4 or 6 jaw meter base, wall or pole bracket |
| Dimensions: | 15.25"h x 9.25"w x 8.50"d |
| Environmental | |
| Operating Temperature: | -40C to 80C (-40CF to +176F) |
| Humidity Range: | 0 to 95% (non-condensing) |
| Measurement Performance | |
| Voltage Secondary Resolution: | 0.1 Vac |
| Accuracy: | ± 0.5% of reading over temperature. |
| Range: | Same as operating range, true rms |
| Primary VT Ratio Range: | 1:1 to 1000:1 in 0.1:1 increments |
| Current | |
| Resolution: |
Fisher Pierce 1301 sensor: 0.1A Lindsey line post sensor: 0.1A Current transformer: 0.01A (secondary) |
| Accuracy: | ± 1.0% Reading, ± 0.2 Range, ± sensor error. |
| Range: | Fisher
Pierece 1301 sensor ...4-800A true rms Lindsey line post sensor: 4-800A true rms. Current transformer: 0.1-20A (secondary) true rms Current Transformer Ratio (CTR): 5:5 to 2000:5 in 1:5 increments. |
| Reactive Power (VAr) | |
| Resolution: | 1 kVAr |
| Range: | ± 99,999k VAr |
| Time Clock | |
| Resolution: | 1 second |
| Accuracy: | ± 10 minutes per year |
| Range: | 24 hour clock |
| Settings: | 1 minute increments |
| Phase Angle | |
| Resolution: | 0.1° |
| Accuracy: | ± 1° |
| Range: | 0° - 359° |
| Neutral Current | |
| Resolution: | Fisher
Pierce AT929 sensor:0.1A Current Transformer: 0.01A (secondary) |
| Accuracy: | ± 1% of reading, ± 0.2% range, ± sensor error |
| Range: | Fisher
Pierce AT929-400 sensor: 1 to 60A Current Transformer Ratio: 5 to 2000:5 Voltage Transformer: 0-120V(secondary) |
| Controller Processor | |
| Memory Size: | 32 kB (standard), 128 kb (option) |
| Memory Types: | EPROM, NVRAM and battery backed RAM |
| Series 1301 Line Post Sensor | |
| Calibration Accuracy at 120A: | ± 1% |
| Linearity Error: | 3-1200A, ± 0.5° |
| Temperature Error: | ± 0.02%/°C |
| 7th Harmonic Response: | 82% |
| *See Fisher Pierce Series 1301 bulletin FP054 for complete specifications. | |
|