| AutoCap?/font> Series 4400 Controller | |
| Voltage Range | |
|
PCC Power & True RMS Sensing |
95-140
V, 60 Hz 190-280 V, 60 Hz 95-125 V, 50 Hz 190-50 V, 60 Hz |
| Sensing
Accuracy: |
± 0.5% of reading over temperature. |
| Voltage
Control and Override: |
95-140 V / 190-280 V secondary in 0.1 V increments. |
| Voltage
Transformer Ration (VTR): |
1:1 to 1000:1 in 0.1:1 increments. |
| Current | |
| Sensors: |
|
| Accuracy: | ± 1.0% Reading, ± 0.2% Range, ± sensor error. |
| Angle Accuracy: | ± 1 deg., ± sensor error. |
| Current
Control - Range/Resolution: |
Line
post sensor ... 4-800A in 0.1 A increments. Current Transformer ... 0.1-2.0A secondary in 0.01A increments |
| Current
Transformer Ratio (CTR): |
5:5 to 2000:5 in 1:5 increments. |
| VAr Control - Range/Resolution | |
| Adaptive VAr: | Limited only by secondary voltage range x current sensing range. |
| 3ø kVAr: | Range ± 1 to 99,999 kVAr in 1 kVAr increments. |
| Time
Control - Range/Resolution: |
Two Close and two Trip settings for each day of the week in 24:00 hour clock, in 1 minute increments. |
| Temperature Control - Range/Resolution | |
| Sensor: | Located on bottom of enclosure with radiation shield. |
| Range: | -40° to +122°F (-40° to +50°C) outside air ambient. |
| Accuracy: | ± 2°F/1°C |
| Temperature
Control, Override, and Bias: |
|
| Serial Communications Port: | DB9 female connector |
| Optical Communications Port: | Type 2 |
| Operating Humidity Range: | 0-95% non-condensing. |
| Surge Withstand: | ANSI C62.41-1987 |
| Electrostatic Discharge Test: | 15kV applied to all accessible parts, IEC 801-2. |
| Output Relay Rating: | 10A continuous. 50A, 50% PF, 6 cycles make only. |
| Relay Type: | Momentary
(two relays). Contact closure period: 1-1000 sec. in 1 sec. increments. 2A controller fuse. |
| Enclosures: | |
| Six Stab Lexan: | 8.5h x 6.5w x 4.0d in. Includes optical port and electromechanical operations counter options. |
| Aluminum: | 11.5 x 7.0w x 4.0d in. Includes optical port and electromechanical counter options. |
| Computer Requirements: | SmartSet setup software requires Windows 3.1 or better. |
| Series 1301 Line Post Sensor | |
| Calibration Accuracy at 120A: | ± 1% |
| Linearity Error: | 3-1200A, ± 0.5° |
| Temperature Error: | ± 0.02%/°C |
| 7th Harmonic Response: | 82% See Fisher Pierce Series 1301 bulletin FP054 for complete specifications. |
|
电话:(86 21) 6432 9508(总机) 直线:(86 21) 6432 9506 传真:(86 21) 6432 9507 邮件: jane.chen@tnb.com |