Joslyn Canada manufactures power transmission and distribution equipment for electric utilities - reclosers  
Joslyn Hi-Voltage manufactures power transmission and distribution equipment for electric utilities - reclosers


     

   
  
1. ELECTRICAL
  a) Contact material shall be silver impregnated/silver plate copper. They shall use a ball and socket design for ease of alignment and to allow for residual vibration and forces created by winds.
  b) Contact pressure shall be supplied by springs remote from the current conductors, and in no way should be part of the current carrying path.
  c) Termination of wire should be to crimp type connectors.
  d) Electrical insulation of contacts should be provided by porcelain standoffs.
  e) Lowering device should be make and break rated so that the fixture need not be remotely isolated before lowering. These make and break ratings shall be as follows: 250 VAC - 30 amps 600 VAC - 15 amps 250 VDC - 10 amps
  f) Lowering device shall have (4) contacts as standard.
  
2. MECHANICAL OPERATION
  a) System shall support weight of all Obstruction Lights available in the classification of the specified Obstruction lights, so that substitutions can be made without major disruption of the system.
  b) System shall be operated by portable winch with separate operating line and winch line or fixed winch with a continuous operating line and winch line supplied by the lowering device manufacturer.
  c) Device shall be manufactured with cast aluminum for the housing.
  d) Operation must be a slow pull/quick release method. This movement shall be facilitated be a trip lever provided by the lowering device manufacturer.
  e) Device shall be of a maintenance-free design.
  f) Latching shall be a single point centered design to facilitate even wear over the life of the hanger.
  
3. SYSTEM
  a) Upper or fixed housing of lowering devices shall contain: aa. attached pulley bb. single point latching mechanism cc. guide dd. upper (socket) electrical contacts ee. mast arm for attachment of device to structure ff. termination location for for fixture guide line
  b) Lower or moveable housing of lowering device shall contain: aa. operating line termination bb. positioning stem and latch assembly cc. lower (ball) electrical contacts dd. fixture adapter
  c) Fixtures shall be lowered on a guide line to allow operation of system in adverse weather and structural clearance. The angles of the guide line to the structure shall be to lowering device manufacturer's instructions.
  d) Operating line shall be special quality high strength/high flexibility stainless steel and be supplied by the lowering device manufacturer.
  e) Each turn in the structure must provide a transitional pulley assembly for the operating line consisting of pulleys, and flare ends (if enclosed in conduit) to prevent cable rub and/or snags on the conduit runs.
  f) Each operating line run shall be encased in conduit or supported by pulleys placed at intervals suggested by the lowering device manufacturer.
  

  
  
  
Manufacturers reclosers and power transmission and distribution equipment for electric utilities
主页
 | 关于我们 | 产品介绍 | 资料下载 | 联系我们

美国乔世林高压公司 中国.上海 徐汇区漕宝路80号光大会展中心D座1406室 邮编:200235
电话:(86 21) 6432 9508(总机) 直线:(86 21) 6432 9506 传真:(86 21) 6432 9507 邮件: jane.chen@tnb.com