The Joslyn SF6 load break switch has three position switches that allow close-open-ground or close-open-test ground switching. Applications include indoor, outdoor, subsurface, and padmount applications for systems rated 15kV and 27kV. Rated load break switching of 200 or 600 Amperes. The corrosion-resistant tank is constructed of stainless steel and is completely sealed.

            
Easy to Operate Recloser
  Sequences are controlled by one single operating handle
Three Positions
  Three phase, three position (close/open/test/ground position) with 2, 3, or 4 way configuration
Puffer Contact System
  Provides efficient arc extinction combined with an internal absorbent to limit by-product formation
Rugged Construction
  Coal tar epoxy stainless steel tank provides deadfront, compact, sealed construction and prevents corrosion
SCADA Compatible
  Manually operated with optional motor operators
         
Specifications

SF-6 Ratings
Maximum Design Voltage
15kV
27kV
Frequency
50/60 Hz
50/60 Hz
BIL Impulse Withstand
95kV
125kV
One Minute AC Withstand
35kV
60kV
Fifteen Minute DC Withstand
53kV
78kV
Corona Extinction @ 3PC
11kV
19kV
Load Interrupting & Load Switching
600 Amps
600 Amps
Transformer Magnetizing Interrupting
21 Amps
25 Amps
Capacitor & Line Charging Interrupting
27 Amps
40 Amps
Asymmetrical Momentary*
22.5kA
22.5kA
3 Operation Fault Close*
22.5kA
22.5kA
Symmetrical 1 Second Rating*
15kA
15kA
Continuous Current Rating*
600 Amps
600 Amps
8 Hour Overload Current*
900 Amps
900 Amps
Overload Interrupting Capability 10 Operations
1400 Amps
1400 Amps
Operations - 600 Amp Load Interrupting Endurance
500
500
Open Gap BIL Flashover Withstand
145kV
145kV
Mechanical Life Operations
2000
2000
SF-6 Gas Normal Operating Pressure
2-15 PSIG
2-15 PSIG
Maximum Gas Leakage cc/second
10 - 7
10 - 7
ASTM B-117 Corrosion Resistance in Hours
2000
2000
Fault Withstand Symmetrical "Phase-to-Phase" - 22 Cycles
12kA
12kA
Internal Fault Withstand Before Venting - 40 Cycles
5kA
5kA
*NOTE: When 200 amp elbow connections are specified, the continuous current, overload, momentary and one-second ratings will be derated. Typically 200 Amp accessories are rated 200 Amp continuous, 300 Amp 8 hour overload, 15kA ASYM momentary and 10kA for 1/2 second.

SF-6 Ordering Information
SWITCH
CONFIGURATION
CATALOG NO.
MAXIMUM VOLTAGE

WEIGHT (lbs.)
(approximate)

WIDTH (in.)

2 Way/1 Switched Way
(right or left hand operation)

SG6TG-21-15
SG6TG-21-27
15.5kV
27kV
450 lbs.
450 lbs.
35"
35"

2 Way/2 Switched Ways
(right or left hand operation)

SG6TG-22-15
SG6TG-22-27
15.5kV
27kV
500 lbs.
500 lbs.
35"
35"
3 Way/3 Switched Ways
(right or left hand operation)
SG6TG-33-15
SG6TG-33-27
15.5kV
27kV
680 lbs.
680 lbs.
50"
50"
4 Way/4 Switched Ways
(right or left hand operation)
SG6TG-44-15
SG6TG-44-27
15.5kV
27kV
900 lbs.
900 lbs.
65"
65"
 

Options and Accessories

Viewing Windows - Allow visual confirmation of contact position
Ground Test Bushings - Provide convenient disconnecting, ground and test of incoming lines
Motor Operators - For remote operation (Available on multi-way switches)
Remote Supervisory - Control packages with battery back-up
Padmount - Enclosed padmount unit
  

  
  
  
Manufacturers reclosers and power transmission and distribution equipment for electric utilities