Adaptive
VAr?b> Control |
| |
Automatically
measures the size of the bank, and establishes VAr set points for maximum
energy loss reduction. |
 |
Adaptive
Voltage Guard?/font> |
| |
Identifies
voltage change from bank switching and inhibits Close operation if Voltage
Guard plus present line voltage exceeds high voltage limit. |
 |
PhaseFind
Function |
| |
Locates current signal phase with respect to voltage phase and compensates
for phase rotation and reversed wiring. |
 |
Reverse
Power Functions |
| |
Calculates proper Var setpoints to compensate for altered Var measurement
in this condition. |
 |
Reverse
Trip/Close Detection |
| |
Automatically
senses reverse wiring of the Close and Trip drive circuits which inhibits
all switching (except manual). |
 |
Anti-hunt
Function |
| |
Automatically
compensates for rapid bank tripping due to cycling loads or interaction
from other switched banks on the feeder. |
 |
Undervoltage
Inhibit |
| |
Protects
the capacitor bank switch from damage caused by low voltage. |
 |
Ordering
Information |
| Example |
| Model: |
| 45 |
1 |
1 |
N |
- |
C |
T |
S |
- |
D |
D |
A |
- |
SK |
6 |
1 |
A |
|
| Section: |
| 1 |
2 |
3 |
4 |
- |
5 |
6 |
7 |
- |
8 |
9 |
10 |
- |
11 |
12 |
13 |
14 |
|
| Section
1 |
Basic
Model Number |
| 45 |
Autocap
programmable capacitor with two-way communications |
| Section
2 |
Line
Current Input (Current sensing device ordered separately |
| 1 |
Fisher
Pierce 1301 line post sensor (60A/V) or Lindsey sensor (100A/V) |
| 2 |
CT (5A
secondary) |
| 0 |
None |
| Section
3 |
Neutral
Current Sensor |
| 1 |
Fisher
Pierce AT929 sensor with 6 foot lead (supplied) |
| 2 |
CT (not
supplied) |
| 3 |
VT (not
supplied) |
| 0 |
None |
| Section
4 |
Optical
Communication Port |
| F |
Supplied |
| N |
None |
| Section
5 |
Counter/Display |
| C |
Electro-mechanical
(counter 120 Vac only) |
| D |
2-line
display only (read only) |
| E |
Electromechanical
counter and 2-line display (read only) |
| N |
None |
| Section
6 |
Temperature
Sensor |
| T |
Supplied |
| N |
None |
| Section
7 |
Memory |
| S |
Standard
32K |
| E |
Expanded
128K |
| Section
8 |
Communications
Protocol |
| F |
SmartSet
(No comm. micro or flash memory) |
| D |
DNP 3.0
(comm. micro and flash memory installed) |
| |
Note:
For cellular phone or modem communication, select "F" |
Section
9
& 10 |
Communications
Options |
| BA |
Installed-Metrocom
model 20043 |
| BB |
Radio
Ready |
| DA |
Installed-MDS
model 9310, 9810 |
| DB |
Radio
Ready |
| NC |
Communications
ready or radio upgrade |
| Note: |
- Installed=Radio
installation by FP, supplied by customer. Communication micro, flash
memory and power supply included.
- Radio Ready=
Radio installed by customer. Radio bracket, antenna mount and cables
included.
Communication micro, flash memory & power supply included.
- Communications
Ready (defined by selecting "D" in section 8)= Radio bracket
an cables not included.
- Power supply
included. Comm. micro and memory installed.
- Radio Upgrade
(defined by selecting code "F" in section *)=Radio bracket
and cables not included. Comm. micro and memory not installed (Controller
board change out required for communications using a protocol other
than SmartSet).
|
| Section
11 |
External
Wiring and Mounting Configuration |
| |
Section
11 Four Jaw Meter Socket Mounting and Wiring
Section
11 |
1 |
2 |
3 |
4 |
5 |
6 |
External
ND Lug |
Current
Inputs |
| FJ |
L |
N/GND |
TR |
CL |
- |
- |
NO |
NONE |
| GJ |
L |
N/COM |
TR |
CL |
- |
- |
YES |
NONE |
Section 11 Six Jaw
Meter Socket Mounting and Wiring
Section
11 |
1 |
2 |
3 |
4 |
5 |
6 |
External
GND Lug |
Current
Inputs |
| SJ |
CSL |
N/GND |
L |
TR |
CSH |
CL |
NO |
LINE
ONLY |
| TJ |
CSL |
N |
L |
TR |
CSH |
CL |
YES |
LINE
ONLY |
| SM |
L |
N/GND |
CSL |
CSH |
TR |
CL |
NO |
LINE
ONLY |
| TM |
L |
N |
CSL |
CSH |
TR |
CL |
YES |
LINE
ONLY |
| SL |
L |
N/GND |
NSL |
NSH |
TR |
CL |
NO |
NEUTRAL
ONLY |
| TL |
L |
N |
NSL |
NSH |
TR |
CL |
YES |
NEUTRAL
ONLY |
| SK |
L |
N/GND/COM |
NSH |
CSH |
TR |
CL |
NO |
LINE+NEUT |
| TK |
L |
N/COM |
NSH |
CSH |
TR |
CL |
YES |
LINE+NEUT |
Section 11 Bracket
Mounting with Terminal Strip
Section
11 |
|
External
GND Lug |
Current
Inputs |
BJ:
POLE
WJ: WALL |
WIRE
TO TERMINAL STRIP AS SHOW BELOW |
YES |
NONE,
LINE, NEUTRAL OR LINE+NEUTRAL |
Terminal Strip (Aluminum
Enclosure Only)
Socket for CT shorting
switch available for SJ & TJ wiring
 |
GND=System
ground
N = Neutral
L = Line
RLY = Output relay armatures
CL = Close
TR = Trip
CSH = Line current signal High
CSL = Line current signal Low
NSH = Neutral current signal High
NSL = Neutral current signal Low
|
|
View looking
into socket
|
 |
| *
Broken lines between terminals indicate removable jumper |
|
| Section
12 |
Enclosure
Type |
| 6 |
Luran |
| Section
13 |
Voltage/Frequency |
|
1
|
120 Vac,
60 Hz |
| 2 |
240 Vac,
60 Hz |
| 3 |
120 Vac,
50 Hz |
| 4 |
220 Vac,
50 Hz |
| 5 |
240 Vac,
50 Hz |
| Section
14 |
Factory
Code |